Houston Utility Service WWR unit
Untitled design (1).png

System

Manufacturer: Houston Utility Service

Make: WWR Mark IV

Type: Fully automated PLC controlled unit

Process: Aerobic waste water processing unit

Volumes

Weight: 8,377 lbs (3800kg) empty on skid

10,362 lbs (4700kg) mounted on skid

24,560 lbs (11140kg) working (no skid)

26,544 lbs (12040kg) mounted on skid

Fluid Capacity: 1939 gal (7340L)

Compartments:

1. Balance tank 248 gal (940L)

2. Separator chamber 346 gal (1310L)

3,4&5 Aeration chambers 1038 gal (3930L)

6. Sedimentation chamber 214 gal (810L)

7. Chlorination tank 92 gal (350L)

Electrical

Control: Micrologix PLC

Power Supply: 240Volts 20 amps

Metering Pump: VFD controlled CP 800 Mono Pump 16 gal/min @ 16.5’

Pump Out Pump: 240 V CP 25 mono 6.6 gal/min @ 16.5’ Sludge Return Pump: 240 V Cp 25 mono 6.6 gal/min @ 16.5’ Aeration Pumps: 3 x 240V Thomas Gardner Denver LP150 HN UV Systems: Sterilight silver S12Q-PA

Chlorination System: Solenoid driven metering pump VMS MF

Sewage Inlets

  • 11 x 2” female camlock fittings

  • 1 x 1 ¼” female camlock fitting for kitchen waste (if stand-alone)

Parameters

  • BOD: <65 (mg/l)

  • Ecoli: <75 CFU/100 (ml)

  • pH: 6.0 – 9.0 (SU)

  • Chlorine Residual: 2 – 3 (mg/l)

Engineering

  • NATA approved water engineer designed

  • Calculated through the Biowin modelling method

Benefits

  • Plug and play for easy set up

  • Reduces amount of Trucks on the road

  • No Transport of waste disposal

  • Very low maintenance

  • Scalable for operations of larger accommodation

  • Rigid construction

  • Unit is transported full no requirement to pump out

  • Treats kitchen & laundry waste through a grease trap

  • Controlled irrigation. Dust Suppression, down-hole purposes

  • External valve for treated effluent

  • Each unit can process up to 10,000 litres per day (20 personnel)

  • Engineered to provide “CLASS A” waste dispersed through irrigation system

  • Engineer designed to Australian standards